Seite 1 - Input Module Catalog Number:

0300169-01 Rev. C32-Channel Analog Input Module(Cat. No. Quantum Automation Series 140 AxI 05x 00sc)Installation Instructions Input Module Catalog Num

Seite 2

1.3 Related Publications Modicon Modsoft Programmer User Manual. 890 USE 115 00 Modicon TSX Quantum Automation Series Hardware Reference Guide.

Seite 3

Chapter 2MODULE SETUP FOR MODSOFT2.1 General InformationSix steps must be performed in order to fully configure the Quantum systemin preparation for u

Seite 4

2.2 Installation of new run time filesIf you are using the Modsoft programming software version 2.4 or 2.5, it isnecessary to update the following run

Seite 5 - Table Of Contents

4x Configuration Word 3x + 0 Data Input Word 14x+1 *Time of Day Clock Control Word 3x + 1 Data Input Word 24x+2 Day of Week (Sun+1 Mon+2 etc.) 3x + 2

Seite 6

 Calibration rate Filter Frequency Selection Input Data Format Input Range Differential ModeThe primary zoom screen for this module is shown

Seite 7 - OVERVIEW

Once at power up onlyEvery 1 minEvery 10 min [default]Every 30 minSelecting an autocalibration schedule rate is an exercise in tradeoffs.Performing au

Seite 8 - 1.1 Inputs

+ Note: The modules format selection must be compatible with the register formatselected in Modsoft.❑ Input Range: Module must support c

Seite 9 - 1.2 LEDs

Figure 2.3❑ Alarm Enable: The second zoom screen, shown in figure 2.2, allowsthe user to enable or disable alarms. Alarms are disabled by default.I

Seite 10 - 1.3 Related Publications

12Installation Instructions32-Channel Analog Input ModuleQuantum Series 140 ACI 052 00scTime stamp channel select (4x+0 bits 13-16)0000 = Channels 1-2

Seite 11 - MODULE SETUP FOR MODSOFT

Chapter 3MODULE SETUP FOR CONCEPT3.1 General InformationSix steps must be performed in order to fully configure the Quantum systemin preparation for u

Seite 13 - 2.4 Zoom Screen Configuration

3.2 Installation of new run time filesThe 140 ACI 052 00sc is manufactured by Spectrum Controls, Inc. Followthe Concept installation procedure for ou

Seite 14

The register data formats are discussed in the following section.4x Configuration Word 3x + 0 Data Input Word 14x+1 *Time of Day Clock Control Word 3

Seite 15

3.4 Concept I/O Map Module Parameters:Concept programming software does not implement zoom screens forModConnect partner modules and allows only direc

Seite 16

Selecting Input Ranges: Register 11 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Default=0x2000 (0x2924 for 140 ACI 050sc)NU NU Input Range Group 1Input Rang

Seite 17

Selecting Filter Frequencies: Register 11 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Default=0x2000 (0x2924 for 140 ACI 050sc)NU NU Filter Frequency Group

Seite 18

Selecting Data Format: Register 21 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Default=0x2A92NU NU NU NU Data Format Group 1Data Format Group 2Data Format

Seite 19 - MODULE SETUP FOR CONCEPT

Selecting Channel Acquisition Mode: Register 31 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Default=0x8205NU NU NU NU NU NU NUAcquisition Mode Group 1Acqui

Seite 20

Selecting the Calibration Rate: Register 31 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Default=0x8205NU NU NU NU NUCalibration RateCalibration Rate:Bit 7 B

Seite 21

Selecting the Calibration Rate: Register 31 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Default=0x8205Time Stamp/Alarm Mode DisableTime Stamp/Alarm Trigger

Seite 22

231 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Reg 4 Chans 1-4 Min Limits1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Reg 5 Chans 1-4 Max Limits1 2 3 4 5 6 7 8 9

Seite 23

PREFACE☞ Note: Power, input and output (I/O) wiring must be in accordance with Class I, Division 2 wiringmethods [Article 501-4 (b) of the National

Seite 24

24Installation Instructions32-Channel Analog Input ModuleQuantum Series 140 ACI 052 00sc3.5 Spectrum I/O Configuration UtilitySCIOCFG.EXE is a utili

Seite 25

3.6 SCIOCFG.EXE Installation:SCIOCFG.EXE is a 32-bit Windows program requiring Windows 95 ornewer. Installation of SCIOCFG.EXE is simple. Copy the S

Seite 26

The SCIOCFG.EXE should be running as a background task, wheneverConcept software is being used to change the configuration registers of the140 AxI 05x

Seite 27

Chapter 4MODULE CONFIGURATION AND STATUSThe 140 ACI 052 00sc uses a total of nine 3x level and nine 4x level registers. After Modsoft (Section 2.3)

Seite 28

Bit 8: Channels 1-4Bit 7: Channels 5-8Bit 6: Channels 9-12Bit 5: Channels 13-16Bit 4: Channels 17-20Bit 3: Channels 21-24Bit 2: Channels 25-28Bi

Seite 29

4x Group Select: Bits 13, 14, 15, 16These four bits are used to select a desired group of channels when theAuto Sequence mode is not used. The grou

Seite 30

4.2 Time of Day Configuration (Register 4x+1 to 4x+8)4x Configuration Word 3x + 0 Data Input Word 14x+1 *Time of Day Clock Control Word 3x + 1 Data In

Seite 31 - 3.6 SCIOCFG.EXE Installation:

4.3 Module status information (Register 3x+8)The information provided in this register is generic information about thismodule. Bits 1-8 and 10 provi

Seite 32

3x+8 Configuration Error: Bit 10An illegal configuration was attempted. When this occurs configuration willnot be accepted by the module and this fl

Seite 33 - Chapter 4

4.4 Channel Status (Registers 3x+ 0 through 3x+7)As described in Section 2.5, register 4x bits 1and 2 can be set to allowmonitoring of individual chan

Seite 34

WARNINGEXPLOSION HAZARDWhen in hazardous locations, turn off power before replacing or wiringmodules.iiInstallation Instructions32-Channel Analog Inpu

Seite 35

3x+0 . . . 7 Under Range Flag: Bit 4This is a nonfatal under range flag. The bit is set to 1 when an input valueis read within one count of the m

Seite 36

35Installation Instructions32-Channel Analog Input ModuleQuantum Series 140 ACI 052 00sc Filter Selection BitsBit 10 Bit 11 -3db Filter Frequency0 0 2

Seite 37

36Installation Instructions32-Channel Analog Input ModuleQuantum Series 140 ACI 052 00scThe time stamp data is stored in eight registers. Each group

Seite 38

Chapter 5INSTALLATION☞ Note: When field wiring the I/O modules, the maximum wire size that should be used is 1-14AWG or 2-16 AWG; the minimum size i

Seite 39

WARNINGELECTROSTATICALLY SENSITIVE COMPONENTSEXPLOSION HAZARDSubstitution of compnents may impair suitability for Class I, Division 2.WARNINGEXPLOSION

Seite 40

Before installing the module, you should: Configure all of the appropriate zoom screen, configuration and othernecessary set up according to Chapter

Seite 41

5.2 Single Ended Field Wiring Example2143658710 912 1114 1316 1518 1720 1922 2124 2326 2528 2730 2932 3134 3336 3538 3740 3940Installation Instruction

Seite 42

41Installation Instructions32-Channel Analog Input ModuleQuantum 140 ACI 052 00sc5.3 Differential Field wiringDifferential mode performs a software di

Seite 43 - INSTALLATION

42Installation Instructions32-Channel Analog Input ModuleQuantum 140 ACI 052 00sc5.4 Differential Field Wiring Example2143658710 912 1114 1316 1518 17

Seite 44

Chapter 6APPLICATION NOTES6.1 General Application TipsThe following is a list of dos and donts that should be observed in yourapplications. Select

Seite 45 - 5.1 Field Wiring

Table Of ContentsCHAPTER 1: OVERVIEW ... 11.1 Inputs...

Seite 46 - Quantum 140 ACI 052 00sc

6.2 Demultiplexing Channel Data - Autosequence ModeThe autosequence mode of operation is intended to simplify the demultiplexingof channel data from t

Seite 47 - 5.3 Differential Field wiring

The I/O map is as follows: (Manual Mode)45Installation Instructions32-Channel Analog Input ModuleQuantum 140 ACI 052 00scRack Slot Module Input Ref O

Seite 48

The following ladder logic shows how to move data from the 8 multiplexedinput words to a block of 32 output words starting at location 400101 using t

Seite 49 - APPLICATION NOTES

Filter -3db 1 channel 32 channelFrequency Frequency Update Time Update time10 Hz 2.62 Hz 308 ms 9.9 sec50 Hz 13.1 Hz 68 ms 2.2 sec60 Hz 15.7 Hz 58 ms

Seite 50

6.6 Range and Data Format SelectionEach of the modules input ranges can be viewed in one of the four datain formats below. The table shows the mini

Seite 51

Chapter 7TROUBLESHOOTING7.1 General InformationReview of the Module Setup Procedures in Section 2.1 is recommendedprior to following the troubleshooti

Seite 52 - 6.4 Channel Update Rate

STEP 3: Check the modules fault LED.VERIFY: The modules red FAULT LED is off. This LED indicates amodule hardware error.CORRECTIVE ACTION: The m

Seite 53

51STEP 4: Check the modules communication status.VERIFY: The modules green ACTIVE LED is on. This indicates that themodule is communicating prope

Seite 54

52Installation Instructions32-Channel Analog Input ModuleQuantum 140 ACI 052 00sc

Seite 55 - TROUBLESHOOTING

53Installation Instructions32-Channel Analog Input ModuleQuantum 140 ACI 052 00scChapter 8SPECIFICATIONSNumber of Channels 32Input Registers Required

Seite 56

Installation Instructions32-Channel Analog Input ModuleQuantum 140 ACI 052 00scCHAPTER 6: APPLICATION NOTES...

Seite 57

Engineering units mV, mAResolution 10 bits to 22 bits (frequency dependent)Input Filter 10Hz, 50Hz, 60Hz, 1KHzDigital Notch Filter, Programmable in gr

Seite 58

NoticeThe products and services described in this publication are useful in a wide variety ofapplications. Therefore, the user and others responsible

Seite 59 - SPECIFICATIONS

ModSoft is a registered trademark of Schneider Electric, Inc. Copyright © 2000 Spectrum Controls, Inc. All rights reserved.Specifications subject to c

Seite 60

Chapter 1OVERVIEWThe Time Stamp is one out of a series of four modules. The differentiationbetween the four different modules is shown in the table b

Seite 61

1.1 InputsThe 32 channels are separated into four groups of eight. Each group can beconfigured for a different voltage or current range. The ranges

Seite 62

1.2 LEDsThe module has a front LED panel that includes 35 LEDs:Ready LED -1 Green LED indicates modules self test has passed and is ready tocommuni