User’s Manual Pub. 0300272-01 Rev. A.0 Point IO™ 2 Channel Isolated Output Analog HART Module Catalog Number: 1734sc-OE2CIH

Seite 2

1-2 Chapter 1: Module Overview User’s Manual Pub. 0300272-01 Rev. A.0 Section 1.3 Output Types The OE2CIH module supports two, user-selectable, curr

Seite 3 - Important Notes

Chapter 1: Module Overview 1-3 User’s Manual Pub. 0300272-01 Rev. A.0

Seite 4

1-4 Chapter 1: Module Overview User’s Manual Pub. 0300272-01 Rev. A.0 1.5.1 LED Indicators The 1734 analog HART module uses several LEDs to show oper

Seite 5 - Table of Contents

Chapter 1: Module Overview 1-5 User’s Manual Pub. 0300272-01 Rev. A.0 Section 1.6 System Overview The module communicates to the controller via

Seite 6

1-6 Chapter 1: Module Overview User’s Manual Pub. 0300272-01 Rev. A.0 See the block diagram below.

Seite 7

User’s Manual Pub. 0300272-01 Rev. A.0 Chapter 2 Installation and Wiring This chapter will cover:  Compliance to European Union directives  P

Seite 8 - Used in This

2-2 Chapter 2: Installation and Wiring User’s Manual Pub. 0300272-01 Rev. A.0 Section 2.2 Power Requirements The module receives power through the

Seite 9 - Module Overview

Chapter 2: Installation and Wiring 2-3 User’s Manual Pub. 0300272-01 Rev. A.0 WARNING Explosion Hazard  Substitution of components may imp

Seite 10

2-4 Chapter 2: Installation and Wiring User’s Manual Pub. 0300272-01 Rev. A.0 analog module. Position the module:  Away from sources of electrical

Seite 11

Chapter 2: Installation and Wiring 2-5 User’s Manual Pub. 0300272-01 Rev. A.0 2.4.2 Install Mounting Base WARNING Hazard of damage to mo

Seite 12 - 1.5.1 LED Indicators

ii Point IO™ 2 Channel Isolated Output Analog HART Module User’s Manual Pub. 0300272-01 Rev. A.0

Seite 13 - 1.6.2 Module Operation

2-6 Chapter 2: Installation and Wiring User’s Manual Pub. 0300272-01 Rev. A.0 2.4.3 Install the Output Module The module can be installed before, or

Seite 14

Chapter 2: Installation and Wiring 2-7 User’s Manual Pub. 0300272-01 Rev. A.0 1. Using a bladed screwdriver, rotate the key switch on the mounti

Seite 15 - Installation and Wiring

2-8 Chapter 2: Installation and Wiring User’s Manual Pub. 0300272-01 Rev. A.0 Section 2.5 Field Wiring Connections Consider the following when wirin

Seite 16

Chapter 2: Installation and Wiring 2-9 User’s Manual Pub. 0300272-01 Rev. A.0 Noise Prevention  Route field wiring away from any other wiring a

Seite 17 - 2.3.3 Remove Power

2-10 Chapter 2: Installation and Wiring User’s Manual Pub. 0300272-01 Rev. A.0

Seite 18 - 2.4.1 Before You Begin

User’s Manual Pub. 0300272-01 Rev. A.0 Chapter 3 Configuring the Module with RSLogix™ 5000 This chapter covers software configuration of the modu

Seite 19 - 2.4.2 Install Mounting Base

3-2 Chapter 3: Configuring the Module User’s Manual Pub. 0300272-01 Rev. A.0 3. From the Controller Organizer:I/O Configuration folder, select the 1

Seite 20

Chapter 3: Configuring the Module 3-3 User’s Manual Pub. 0300272-01 Rev. A.0 The Select Module dialog appears: 5. From this dialog, select the

Seite 21 - 2.4.5 Remove a Mounting Base

3-4 Chapter 3: Configuring the Module User’s Manual Pub. 0300272-01 Rev. A.0 The Select Major Revision dialog appears: 6. Select the major software

Seite 22 - Connections

Chapter 3: Configuring the Module 3-5 User’s Manual Pub. 0300272-01 Rev. A.0  Revision. Revision is divided into major and minor revision value

Seite 23 - 2.5.1 Wiring Diagram

Point IO™ 2 Channel Isolated Output Analog HART Module iii User’s Manual Pub. 0300272-01 Rev. A. Important Notes 1. Please read all the info

Seite 24

3-6 Chapter 3: Configuring the Module User’s Manual Pub. 0300272-01 Rev. A.0 Example dialog filled in: 9. After you have added the local Ethernet c

Seite 25 - RSLogix™ 5000

Chapter 3: Configuring the Module 3-7 User’s Manual Pub. 0300272-01 Rev. A.0 12. The Select Major Revision dialog appears. Enter or select Major

Seite 26

3-8 Chapter 3: Configuring the Module User’s Manual Pub. 0300272-01 Rev. A.0 Example Completed Dialog: 15. You may see another dialog for Connectio

Seite 27

Chapter 3: Configuring the Module 3-9 User’s Manual Pub. 0300272-01 Rev. A.0 17. Make sure the By Vendor tab at the base of the dialog is select

Seite 28

3-10 Chapter 3: Configuring the Module User’s Manual Pub. 0300272-01 Rev. A.0 The New Module dialog appears: View or specify the following options:

Seite 29

Chapter 3: Configuring the Module 3-11 User’s Manual Pub. 0300272-01 Rev. A.0 The new module appears in your hierarchy:

Seite 30

3-12 Chapter 3: Configuring the Module User’s Manual Pub. 0300272-01 Rev. A.0

Seite 31

User’s Manual Pub. 0300272-01 Rev. A.0 Chapter 4 OE2CIH and HART This chapter describes how to read and write HART data using the OE2CIH module.

Seite 32

4-2 Chapter 4: OE2CIH and HART User’s Manual Pub. 0300272-01 Rev. A.0 If the channel is HART-enabled, to determine if a HART device is present on a g

Seite 33

Chapter 4: OE2CIH and HART 4-3 User’s Manual Pub. 0300272-01 Rev. A.0 has been refreshed by the module, and you should re-send the Read Additiona

Seite 34

iv Point IO™ 2 Channel Isolated Output Analog HART Module User’s Manual Pub. 0300272-01 Rev. A.0 Microsoft and Microsoft Windows

Seite 35

4-4 Chapter 4: OE2CIH and HART User’s Manual Pub. 0300272-01 Rev. A.0 Commands sent at Initial Device Connection Command: Definition: Comment: 2 Read

Seite 36

Chapter 4: OE2CIH and HART 4-5 User’s Manual Pub. 0300272-01 Rev. A.0 All three interface types have equal priority:  The User Ladder interface

Seite 37 - OE2CIH and HART

4-6 Chapter 4: OE2CIH and HART User’s Manual Pub. 0300272-01 Rev. A.0 4.2.6 DeviceNet Object This object class configures port attributes such as bau

Seite 38

Chapter 4: OE2CIH and HART 4-7 User’s Manual Pub. 0300272-01 Rev. A.0 Table 4-5 Assembly Object Class Code: 0×04 OE2CIH Instances: #100 = Statu

Seite 39

4-8 Chapter 4: OE2CIH and HART User’s Manual Pub. 0300272-01 Rev. A.0 HART Pass-Through Hold Time This is a module-wide parameter. Valid values are 1

Seite 40 - 38 which will reset the

Chapter 4: OE2CIH and HART 4-9 User’s Manual Pub. 0300272-01 Rev. A.0  Fault Value uses the value set by the user (see below). Program Action.

Seite 41 - 4.2.5 Identity Object

4-10 Chapter 4: OE2CIH and HART User’s Manual Pub. 0300272-01 Rev. A.0 It is considered a configuration error if the values are equal. Negative scali

Seite 42 - 4.2.7 Assembly Object

Chapter 4: OE2CIH and HART 4-11 User’s Manual Pub. 0300272-01 Rev. A.0 To allow the highest resolution for full end-to-end output limits use the

Seite 43

4-12 Chapter 4: OE2CIH and HART User’s Manual Pub. 0300272-01 Rev. A.0 Table 4-8 Input-Only Assembly Instance: ID: Description: Total Size: 100 3 Ch

Seite 44

Chapter 4: OE2CIH and HART 4-13 User’s Manual Pub. 0300272-01 Rev. A.0 Watchdog Fault In the case where the main CPU experiences a watchdog failu

Seite 45

Point IO™ 2 Channel Isolated Output Analog HART Module v User’s Manual Pub. 0300272-01 Rev. A. Table of Contents IMPORTANT NOTES ...

Seite 46

4-14 Chapter 4: OE2CIH and HART User’s Manual Pub. 0300272-01 Rev. A.0 HART STATUS BITS:  INIT = HART device detected  FAIL = No device found or

Seite 47

Chapter 4: OE2CIH and HART 4-15 User’s Manual Pub. 0300272-01 Rev. A.0 HART STATUS BYTE 3: Extended Device Status This is the first byte returned

Seite 48

4-16 Chapter 4: OE2CIH and HART User’s Manual Pub. 0300272-01 Rev. A.0 HART Object CIP HART services will use a subset of the HART Object used in the

Seite 49

Chapter 4: OE2CIH and HART 4-17 User’s Manual Pub. 0300272-01 Rev. A.0 HART Pass-through “Reason Code” definitions The HART Pass-through Reaso

Seite 50

4-18 Chapter 4: OE2CIH and HART User’s Manual Pub. 0300272-01 Rev. A.0 Table 4-13 Read Dynamic Variables (Service Code = 4B) Unconnected Message Fiel

Seite 51

Chapter 4: OE2CIH and HART 4-19 User’s Manual Pub. 0300272-01 Rev. A.0 Request Succeeded Reply HART Read Dynamic Variables - Reply packet structu

Seite 52

4-20 Chapter 4: OE2CIH and HART User’s Manual Pub. 0300272-01 Rev. A.0 Request Succeeded Reply HART Read Dynamic Variables - Reply packet structure R

Seite 53

Chapter 4: OE2CIH and HART 4-21 User’s Manual Pub. 0300272-01 Rev. A.0 Request Failed Reply HART Read Additional Status - Reply packet structure

Seite 54

4-22 Chapter 4: OE2CIH and HART User’s Manual Pub. 0300272-01 Rev. A.0 Table 4-15 Ladder Get Device Information (Service Code = 0×4D) Unconnected Mes

Seite 55

Chapter 4: OE2CIH and HART 4-23 User’s Manual Pub. 0300272-01 Rev. A.0 Request Succeeded Reply HART Get Device Information - Reply packet structu

Seite 56

vi Point IO™ 2 Channel Isolated Output Analog HART Module User’s Manual Pub. 0300272-01 Rev. A.0 4.2.6 DeviceNet Object ...

Seite 57

4-24 Chapter 4: OE2CIH and HART User’s Manual Pub. 0300272-01 Rev. A.0 Request Succeeded Reply HART Get Device Information - Reply packet structure R

Seite 58

Chapter 4: OE2CIH and HART 4-25 User’s Manual Pub. 0300272-01 Rev. A.0 Reply Data HART Ladder Passthrough Init - Reply packet structure Reply Siz

Seite 59

4-26 Chapter 4: OE2CIH and HART User’s Manual Pub. 0300272-01 Rev. A.0 Reply Data HART Ladder Passthrough Query - Reply packet structure Reply Size =

Seite 60

Chapter 4: OE2CIH and HART 4-27 User’s Manual Pub. 0300272-01 Rev. A.0 Table 4-19 Suspend Normal HART Acquisitions (Service Code = 0×51) Unconnec

Seite 61

4-28 Chapter 4: OE2CIH and HART User’s Manual Pub. 0300272-01 Rev. A.0 Request Data Resume Normal HART acquisitions - Request packet structure Reques

Seite 62

Chapter 4: OE2CIH and HART 4-29 User’s Manual Pub. 0300272-01 Rev. A.0 Reply Data Get Single Channel Device - Reply packet structure Reply Size =

Seite 63

4-30 Chapter 4: OE2CIH and HART User’s Manual Pub. 0300272-01 Rev. A.0 HART Processor Detects an Error During startup, the main processor sets a time

Seite 64

User’s Manual Pub. 0300272-01 Rev. A.0 Appendix A This appendix contains configuration information as follows: Table A-1 Environmental Specificat

Seite 65

A-2 Appendix A: Configuration Information User’s Manual Pub. 0300272-01 Rev. A.0 Environmental Tests Industry Standards Test Level Limits Radiated RF

Seite 66 - Declaration of Conformity

Appendix A: Configuration Information A-3 User’s Manual Pub. 0300272-01 Rev. A.0 Table A-2 Safety Tests and Test Limits Safety Tests Industry Sta

Seite 67 - Appendix A

Point IO™ 2 Channel Isolated Output Analog HART Module vii User’s Manual Pub. 0300272-01 Rev. A. Preface Read this preface to familiarize your

Seite 68

A-4 Appendix A: Configuration Information User’s Manual Pub. 0300272-01 Rev. A.0 Table A-4 General Electrical Specifications Parameter Specification

Seite 69

User’s Manual Pub. 0300272-01 Rev. A.0 Index Add On Profile software 3-1 Assembly Object 4-7 Base 1734-TOPS installation 2-7 1734-TOPS removal 2-7

Seite 70

I-2 Index User’s Manual Pub. 0300272-01 Rev. A.0 dialog 3-3, 3-6, 3-8 Technical Assistance 4-31 Technical support contact information vii Who should

Seite 71

User’s Manual Pub. 0300272-01 Rev. A.0

Seite 72

User’s Manual Pub. 0300272-01 Rev. A.0 ©2013 Spectrum ControlsInc. All rights reserved. Specifications subject to change without notice. The Encomp

Seite 73

viii Point IO™ 2 Channel Isolated Output Analog HART Module User’s Manual Pub. 0300272-01 Rev. A.0 Related Documentation The table below provides a l

Seite 74

User’s Manual Pub. 0300272-01 Rev. A.0 Chapter 1 Module Overview Section 1.1 Before You Begin The 1734sc-OE2CIH module has two isolated analog cu