Chapter 4: OE2CIH and HART 4-5
User’s Manual Pub. 0300272-01 Rev. A.0
All three interface types have equal priority:
The User Ladder interface uses a simplified HART interface (EZ-HART) that
only requires the user to send the HART Command number along with its data
bytes (if any) in the request data for the Init Pass-through message without
having to know how to format a real HART message. In addition the Ladder
interface has a MsgReady indicator tag in the Input table to facilitate
determining when the pass-through is complete.
The RSLogix and Asset SW interfaces require creating a complete HART
message (without preambles) as defined by the HART protocol specifications.
A pass-through message is processed with equal priority with the Device Variable scan
command (3 or 9) so the scanning on any one channel looks like this:
4.2.5 Identity Object
This object class supports the Reset service.
Table 4-3 Identity Object
Spectrum Controls
Vendor ID
Initial release will be
1.1
1734sc-OE2CIH 2 PT HART
OUTPUT