32 ControlLogix
Counter Module
StorageMode = 2 - Store/Wait/Resume
StorageMode = 3 - Store-Reset/Wait/Start
StorageMode = 4 - Store-Reset/Start
InputRange[x] 0,1 INT
This setting determines the threshold were the counter will begin to trigger.
Select the range that is best suited to your sensors range.
0= AC 50mVpp threshold
1= AC 200mVpp threshold
2= 5V
3= 12V/24V
KFactor[x] 0 - 1x10
32
FLOAT (C)
The K scale factor is used for counter scaling. This allows users to scale
the counter output into more useful units, like gallons per minute. When a
non-zero Scale Factor value is set the scale calculation is always
performed. A value of zero must be written to the Scale Factor to disable
this feature. This counter value is divided by the K factor. K factors are
positive numbers.
RFactor[x] 0 - 1x10
32
FLOAT (C)
In Program Mode the data value in this register is used for scaling. The
M scale factor is used for meter calibration. When a non-zero Scale
Factor value is set the scale calculation is always performed. A value of
zero must be written to the Scale Factor to disable this feature.